SECTION 271543

Communications Faceplates, Connectors and Patch Cables

Part 1 - General

1.1 Work Included

  1. Provide all labor, materials, tools and equipment required for the complete installation of work called for in the Construction Documents.

1.2 Scope of Work

  1. This document describes the products and execution requirements relating to furnishing and installing faceplates and connectors. Communications faceplates and connectors are covered under this document.
  2. The Communication Equipment Room shall support a minimum of (2) 4-pair Unshielded Twisted Pair (UTP) Copper Cables to each work area outlet unless otherwise noted for specific locations. The cables shall be installed from the Work Area Outlet to the Telecommunications Room (TR) located on the same floor, and routed to the appropriate rack serving that area and terminated as specified in this document. Refer to 27 1500 Section 2.2 for specific workstation cabling requirements.
  3. This section includes minimum requirements for the following:
    1. Faceplates
    2. Copper patch cords and modular connectors
    3. Fiber optic patch cords and modular connectors
    4. Cross Connect Wire
  4. All cables and related terminations, support and grounding hardware shall be furnished, installed, wired, tested, labeled, and documented by the telecommunications contractor as detailed in this document.
  5. Product specifications, general design considerations, and installation guidelines are provided in this document. Quantities of telecommunications outlets, typical installation details, cable routing and outlet types will be provided as an attachment to this document. If the bid documents are in conflict, this specification shall take precedence. The successful vendor shall meet or exceed all requirements for the cable system described in this document.

1.3 Regulatory References

  1. The following industry standards are the basis for the structured cabling system described in this document:
    1. Telecommunications Industry Association / Electronic Industries Alliance (TIA/EIA)
      1. 568-C.0-2012: Generic Telecommunications Cabling for Customer Premises
      2. 568-C.1-2012: Commercial Building Telecommunications Cabling Standard
      3. 568-C.2-2010: Balanced Twisted-Pair Telecommunications Cabling and Components Standards
      4. 568-C.3-2011: Optical Fiber Cabling Components Standard
      5. 568-C.4-2011: Broadband Coaxial Cabling and Components Standard
      6. 569-C-2012: Telecommunications Pathways and Spaces
      7. 606-B-2012: The Administration Standard for the Telecommunications Infrastructure of Commercial Buildings
      8. 607-B-2011: Telecommunications Bonding and Grounding (Earthing) for Customer Premises
      9. 942-A-2012: Standard for Data Centers
    2. National Fire Prevention Act (NFPA)
      1. National Electric Code 2011 (NEC)
    3. International Organization for Standardization (ISO)/International Electrotechnical Commission (IEC)
      1. ISO/IEC 11801 Generic Cabling for Customer Premises
  2. The most recent versions of all documents apply to this project. If there is a conflict between applicable documents, the order above shall dictate the order of precedence in resolving the issue unless an enforceable local or national code is in effect.

1.4 Quality Assurance

  1. Panduit Certification Plus System Warranty
    1. A Certification Plus System Warranty shall provide a complete system warranty to guarantee end-to-end high performance cabling systems that meet application requirements. The guarantee shall include cable and connectivity components and have one point of contact for all cabling system issues. The system shall be warranted for a period of at least 15 years.
  2. Panduit PCI Contractor Agreement
    1. A factory registered Panduit PCI contractor shall complete network installation. The contractor shall have completed standards based product and installation training. A copy of the PCI Contractor Registration shall be submitted in the proposal.
  3. Product Guarantee
    1. All Panduit PAN-NET non-consumable products have a 20-year guarantee. When installed per TIA or ISO/IEC standards, the Panduit PAN-NET Network Cabling System will operate the application(s) for which the system was designed to support. Applications may include, but are not limited to:
      1. 10/100/1000 Mbps Ethernet (IEEE 802.3)
      2. 4/16 Mbps Token Ring (IEEE 802.5)
      3. 155, 622, 1.25 Gbps ATM
      4. SONET e. FDDI/CDDI
      5. IBM System 3x-AS/400
      6. Appletalk
      7. ISDN
  4. In order to qualify for the guarantee, the structured cabling system must be installed per the following:
    1. Meet all TIA/EIA commercial building wiring standards.
    2. Panduit categorized product must be used in conjunction with an equivalent or higher Category UL or ETL verified cable.
    3. Panduit Products must be installed per Panduit instruction sheets.
    4. Note: All Networks shall be installed per applicable standards and manufacturer's guidelines.
    5. If any Panduit PAN-NET product fails to perform as stated above, Panduit will provide new components at no charge.
    6. This guarantee is made in lieu of and excludes all other warranties, expressed or implied. The implied warranties of merchantability and fitness for a particular use are specifically excluded. Neither seller nor manufacturer shall be liable for any other injury, loss or damage, whether direct or consequential arising out of the use of, or the inability to use, the product. Before using, user shall determine the suitability of the product for its intended use, and user assumes all risk and liability whatsoever in connection therewith. The foregoing may not be altered except by an agreement signed by officers of seller and manufacturer.
  5. Where Corning system components are use, a LANscape certified solution is required. Support of 10 Gigabit Ethernet is required.

1.5 Approved Products

  1. Approved faceplate manufacturer: Panduit
  2. Approved surface mount box manufacturer: Panduit, Wiremold
  3. Approved outlet component manufacturer: Panduit
  4. Approved label component manufacturer: Panduit
  5. Approved category 6 module manufacturer: Panduit
  6. Approved category 6 patch cord manufacturer: Panduit
  7. Approved USOC module manufacturer: Panduit
  8. Approved category 6 punchdown 110 style connecting base manufacturer: Panduit
  9. Approved category 5e punchdown 110 style connecting base manufacturer: Panduit
  10. Approved fiber optic patch panel manufacturer: Corning
  11. Approved fiber optic enclosure manufacturer: Corning
  12. Approved fiber optic module/insert manufacturer: Corning
  13. Approved fiber optic connector manufacturer: Panduit, Corning
  14. Approved fiber optic patch cord and pigtail manufacturer: Panduit, Corning

Part 2 - Products

2.1 Equivalent Products

  1. Panduit shall manufacture all products, including but not limited to communications faceplates and connectors. Refer to section 270000 Part 6 regarding substitution of materials.
  2. The outlets and surface mount boxes shall support the network system by providing high-density in-wall, surface mount or modular office furniture cabling applications. The outlets consist of faceplates for flush and recessed in-wall mounting as well as mounting to the modular office furniture systems. The surface mount boxes can be mounted where in-wall applications are not possible or to support applications where surface mount is the best option. All outlets shall utilize fully the interchangeable and individual Mini-Com connector modules that mount side by side to facilitate quick and easy moves, adds and changes. All outlets shall be manufactured from high impact thermoplastic material with a U.L. flammability rating of 94 HB or better. All outlets and surface mount boxes shall be available in four colors including Off White (IW), Electrical Ivory (EI), White (WH) and International Gray (IG).

2.2 Faceplates

  1. Mini-Com Executive Series Faceplates shall be one, two, four and six port vertical single gang and 10 port vertical double gang faceplates with combination head screws, screw covers, labels, label covers and a curved, designer appearance. The faceplates shall mount to standard U.S. NEMA boxes and adapters with screw-to-screw dimensions of 3.28" (83.3mm). The insert labels shall meet UL 969. Each faceplate shall accept Mini-Com modules that can be individually inserted and removed as required. Labeling is required.

    Panduit
    Part Number
    Gang Number of
    Modules
    CFPE2**Y Single 2
    CFPE4**Y Single 4
    CFPE6**Y Single 6
    CFPE10**-2GY Double 10
    ** designates color.    

  2. Wall Phone installation requires a Phone Plate with Module. This is the only component in the Caltech network that do not use the Panduit Mini-Com Executive Series Faceplates since a phone cannot be mounted to that style of faceplate. Contact Panduit technical support to verify mounting holes when using IP or console type telephones. All faceplates supplied with mounting screws. Wall mount faceplate kits only accept wall mountable phones with short patch cord connections to the jack module.

    Panduit
    Part Number
    Gang Description
    KWP6PY Single Stainless steel phone plate with Giga-TX ™ Style Category 6 Keystone Jack Module.

  3. Ultimate ID Products shall provide labeling options that comply with the TIA/EIA-606-A Standard. All products shall be clearly identified with thermal transfer printer (laser printer) technolgoy. Products shall include faceplates, surface mount boxes, patch panels, marker ties, printers and accessories. All label heights shall be the same to allow for consistent labeling. Labeling is required.

    Panduit
    Part Number
    Description Number of
    Modules
    UICFFP4** Snaps into standard knockouts on modular furniture. 4
    ** designates color.    

  4. Mini-Com Modular Furniture Faceplates shall be four-port flat or angled faceplates that snap directly into TIA/EIA standard furniture openings. If required, an extender shall be used with the four port flat faceplate to provide 12.7mm(0.5") additional depth. Each faceplate shall accept Mini-Com modules that can be individually inserted and removed as required. Cutout size requirements are 1.88" to 1.91" (47.80mm to 48.72mm) vertical by 2.98" to 3.03" (74.37mm to 76.96mm) horizontal. Labeling is required.

    Panduit
    Part Number
    Orientation Number of
    Modules
    CFFPL4** Flat with Label 4
    CFFPLA4** Sloped with Label 4
    ** designates color.    

  5. Mini-Com Modular Furniture Faceplates for Four Module Space Herman Miller Ethospace Beltline Furniture Snap-On Faceplate shall be four-port flat or angled faceplates that snap directly into TIA/EIA standard furniture openings. If required, an extender shall be used with the four port flat faceplate to provide 12.7mm(0.5") additional depth. Each faceplate shall accept Mini-Com modules that can be individually inserted and removed as required. Cutout size requirements are 2.38" (60.33mm) vertical by 3.44" (87.31mm) horizontal. Labeling is required.

    Panduit
    Part Number
    Orientation Number of
    Modules
    CFFPL4** Flat with Label 4
    CFFPLA4** Sloped with Label 4
    ** designates color.    

2.3 Surface Mount Boxes

  1. Ultimate ID Products shall provide labeling options that comply with the TIA/EIA-606-B Standard. All products shall be clearly identified with thermal transfer printer (laser printer) generated labels. Products shall include faceplates, surface mount boxes, patch panels, marker ties, printers and accessories. All label heights shall be the same to allow for consistent labeling.

    Panduit
    Part Number
    Orientation Number of
    Modules
    UICBXA12**-A Surface Mount 12
    ** designates color.    

  2. Mini-Com Low Profile Surface Mount Boxes shall be one, two, four, six and 12-port low profile surface mount boxes with a 28mm (1.1”) maximum height. All connections (with exception of the 12 port low profile box) shall exit one side of the box, parallel to the wall. The boxes shall be capable of mounting with screws, adhesive, and/or magnets. The two port boxes shall include a removable blank for addition of a second port. The four, six and 12 port boxes shall include breakouts for use with Pan-Way surface raceway and cable tie slots at each raceway entry point to provide strain relief on incoming cables. The four (except low profile four), six, and 12 port boxes shall include tamper resistant screws that securely fasten the cover to the base and are concealed by screw covers and labels. Each box shall accept individual Mini-Com modules that can be individually inserted and removed as required.

    Panduit
    Part Number
    Max Height (mm) Number of
    Modules
    CBXJ2**-A 23 mm 2
    CBX2**-AY 27 mm 2
    CBXC4**-A 23 mm 4
    CBX4**-AY 28 mm 4
    CBXD6**-AY 26 mm 6
    CBX12**-AY 26 mm 12
    ** designates color.    

  3. Mini-Com Fiber/Multi-Media Surface Mount Boxes shall be six and 12- port surface mount boxes with all connections exiting one side of the box, parallel to the wall. The six and 12 port boxes shall contain a “captive” fiber spool that maintains a minimum 25.4mm (1”) bend radius. The six and 12 port boxes shall store up to 24 meters of buffered optical fiber. The boxes shall be capable of mounting with screws, adhesive, and/or magnets. The boxes shall include breakouts for use with Pan-Way surface raceway on three sides and cable tie slots at each raceway entry point to provide strain relief on incoming cables. The boxes shall include tamper resistant screws that securely fasten the cover to the base and are concealed by screw covers and labels. Each box shall accept Mini-Com modules that can be individually inserted and removed as required.

    Panduit
    Part Number
    Max Height (mm) Number of
    Modules
    CBXF6**-AY 25 mm 6
    CBXF12**-AY 46 mm 12
    ** designates color.    

2.4 Patch Cords, Station Cords and Modular Connectors - Copper

  1. General
    1. The modular connectors and patch cords will be chosen to match the horizontal cabling medium and rating. The same manufacturer shall provide the modular connectors and patch cords. The total patch cord length at the work area is not to exceed three meters (10 ft). Exception: When implementing an open office cabling system as specified under ANSI/TIA/EIA-568-C.1.
    2. The Panduit Mini-Com Network Cabling System or equivalent shall be used for the Work Area subsystem, including all modular connectors. The network cabling system shall be comprised of modular connectors in support of high-speed networks and applications designed for implementation on copper cabling. All outlets shall utilize fully interchangeable and individual connector modules that mount side-byside to facilitate quick and easy moves, adds and changes.
  2. Patch Cords and Station Cords
    1. Copper Patch cables are to be bid as an alternate-add item.
    2. Patch Cords are used to connect network electronics to patch panel ports in the wiring closet.
    3. Patch Cords are to be yellow in color.
    4. Station Cords are used to connect a work station outlet to end user eqiupment.
    5. Station Cords are to be white in color.
    6. Each patch cord is 100% performance tested at the factory and wired T568B.
    7. Constructed of Category 6 (or 6A), 24 AWG UTP stranded cable and TX6 Plus (or TX6A) Modular Plugs; plug contacts plated with 50 microinches of gold for superior performance.
    8. Plug meets all applicable ANSI/TIA-968-A requirements and exceeds IEC 60603-7 specifications.
    9. Slender strain relief boot provides easy access in high density applications, clear in color.
    10. Plug uses an integral pair manager to optimize performance and consistency by reducing untwisting of conductors within the plug.
    11. Labels on patch cords provide identification of performance level, length, and quality control number.
    12. Tangle free latch prevents snags and provides easy release, saving time on frequent moves, adds, and changes.
    13. Category 6A cables exceed requirements of ANSI/TIA/EIA-568-C.2 Category 6A, IEEE 802.3an-2006, and ISO 11801 Class EA channel standards.
    14. Category 6 cables exceed ANSI/TIA/EIA-568-C.2 Category 6 and ISO 11801 Class E standards.
    15. Part Numbers
      Panduit
      Part Number
      Description Function Color Typical Lengths
      UTP6A** Category 6A UTP Patch Cable Station Cable Off White 7, 10, 15, 20
      UTP6X**YL Category 6A UTP Patch Cable Wiring Closet Yellow 6, 7
      UTPSP**Y Category 6 UTP Patch Cable Station Cable Off White 7, 10, 15, 20
      UTPSP**YLY Category 6 UTP Patch Cable Wiring Closet Yellow 6, 7
        **designates length.      

  3. Modular Connectors
    1. Mini-Com Modules for copper shall include the following:
      1. 50 and 75 Ohm BNC coax coupler modules, male-male.
      2. F-Type coax coupler module, male-male threaded.
      3. RCA connector modules with black, red, yellow, and white inserts pass through and punchdown termination types.
      4. S-Video connectors modules - coupler and punchdown termination types.
      5. Blank module to reserve space for future additions.
      6. The connectors shall snap into all Mini-Com outlets and patch panels.
      7. Mini-Com TX6 Plus Jack Modules shall be Category 6 modules featuring GigaTX Technology. The eight position modules shall be used in all work areas and shall exceed the connector requirements of the TIA/EIA Category 6 standard. Termination shall be accomplished by use of a forward motion termination cap and shall not require the use of a punchdown tool. The termination cap shall provide strain relief on the cable jacket, ensure cable twists are maintained to within 1/8” (3.18mm) and include a wiring scheme label. The wiring scheme label shall be available with both T568A and T568B wiring schemes. All terminations for this project shall use the T568B wiring scheme.
      8. The modules shall terminate four-pair 24 and 22 AWG 100 ohm solid unshielded twisted pair cable.
      9. The modules shall be universal in design, including complying with the intermateability standard IEC 60603-7 for backward compatibility. Category 6 modules shall have UL and CSA approval. The modules shall have ETL verified Category 6 performance and ISO Class E performance (as defined in ISO/IEC 11801) in both the basic and channel links. They shall be universal in design, accepting six or eight-pair modular plugs without damage to the outer module contacts. The modules shall be able to be reterminated a minimum of 10 times and be available in 11 standard colors for colorcoding purposes. The module shall snap into all Mini-Com outlets and patch panels.
      10. Part Numbers
        Panduit
        Part Number
        Connector
        Style
        Medium/
        Cable Type
        Termination
        Style
        Insert
        Color
        CJ6X88TG** RJ-45 Category 6A Termination  
        CJ688TG** RJ-45 Category 6 Termination  
        CC688** RJ-45 Coupler Category 6 Coupler  
        CMBA** BNC 50 Ω Coax Coupler  
        CMBA75** BNC 75 Ω Coax Coupler  
        CMF** F Typle 75 Ω Coax Coupler  
        CMFSR**Y F Typle 75 Ω Self Terminating Coax Coupler  
        CJRY** RCA from UTP UTP Punchdown Yellow
        CJRR** RCA from UTP UTP Punchdown Red
        CJRW** RCA from UTP UTP Punchdown White
        CMRPR** RCA from RCA Copper Coupler Red
        CMRPY** RCA from RCA Copper Coupler Yellow
        CMRPW** RCA from RCA Copper Coupler White
        CMRPB** RCA from RCA Copper Coupler Blue
        CMRPG** RCA from RCA Copper Coupler Green
        CMSVC**Y S-Video Copper Coupler Black
        CJSV** S-Video from UTP Copper Punchdown Black
        CMB**-X Blanking Plate N/A N/A  
          **designates color.      

2.5 Patch Cords and Modular Connectors - Fiber

  1. Patch Cords
    1. Fiber Patch cables are to be bid as an alternate-add item.
    2. Patch cables are plenum rated.
    3. Patch cables are duplex.
    4. Patch cable lengths are project specific.
    5. Pass all TIA/EIA-568-B.3 performance requirements.
    6. LC connector housing and boot colors follow TIA/EIA-568-C.3 suggested color identification scheme.
    7. Insertion loss per connection: 0.10dB typical; 0.25dB maximum.
    8. Factory terminated and 100% tested for insertion loss.
    9. Insertion loss data recorded for every patch cord.
    10. Lifetime traceability of test data to a Q.C. number on each patch cord.
    11. Highest quality flame retardant fiber optic cable with tight-buffered coating on each optical fiber.
    12. OM4 patch cords are backward compatible for use with all 50/125μm system requirements.
    13. OM4 patch cords are tested to support network transmission speeds up to 10 Gb/s for link lengths up to 550 meters with an 850nm source per IEEE 802.3ae 10 GbE standard.
    14. OS1 patch cords are 100% factory inspected end face geometry in compliance with Telcordia GR-326-CORE, Issue 3.
    15. Part Numbers
      Manufacturer Part Number Description Medium/
      Cable Type
      Color Typical Lengths
      Panduit FZPE10-10M** LC-LC, Duplex Patch Cable OM4   3, 5, 10, 15, 20
      Panduit F9E10-10M**Y LC-LC, Duplex Patch Cable OS1   3, 5, 10, 15, 20
      Corning 0505C68XD***M LC-LC, Duplex Patch Cable OM4   3, 5, 10, 15, 20
      Corning 0404G68XD***M LC-LC, Duplex Patch Cable OS1   3, 5, 10, 15, 20
          *designates length in meters.      

  2. Modular Connectors - Workstation Outlets
    1. Mini-Com Modules for fiber shall include the following:
      1. TIA/EIA-604 FOCIS-10 compatible adapters.
      2. Exceed TIA/EIA-568-B.3 requirements.
      3. Adapter housing colors follow TIA/EIA-568-C.3 suggested color identification scheme.
      4. Small form factor (SFF) duplex adapter design fits into single module space.
      5. Compatible with Mini-Com products for complete modularity.
      6. Accept FOCIS-10 compatible senior LC connectors at either end and FOCIS-10 junior LC connectors at the inside end for behind the wall applications.
      7. Every adapter is laser marked with Q.C. number to assure 100% traceability.
      8. Part Numbers
        Manufacturer Part Number Connector
        Style
        Medium/
        Cable Type
        Feature/
        Style
        Insert
        Color
        Panduit CMDJLCZBU LC OS1 (9µ) Ceramic Sleeve Blue
        Panduit CMDJAQLCZBL LC OM3 (50µ) Ceramic Sleeve Aqua
        Panduit CMDJAQLCBL LC OM3(50µ) Bronze Split Sleve Aqua

Part 3 - Execution

3.1 Faceplate Configurations

  1. Faceplates are to be Panduit Mini-Com Executive Series Faceplates with four positions unless a requirement for more than four positions is needed (CFPE4xx). Color of faceplate is to match color specified by Caltech for specific location. Locations where more than four positions is needed, use the next larger capacity Panduit Mini-Com Executive Series Faceplates (refer to 271543, Section 2.2.A).
  2. Blank port openings in face plates are to be covered using insert Panduit Blanks where blank color matches faceplate color.
  3. Wallphone Faceplate - 8 conductor. Provide a wall-mounted flush modular faceplate to house a single work area jack. The faceplate shall fit over a standard NEMA dual gang electrical outlet box fitted with a single gang plaster ring cover and shall be stainless steel. The faceplate shall be capable of having a wall-mounted telephone fitted directly over it.
  4. Furniture Faceplate. Provide a flush-mounted modular faceplate to house work area jacks, capable of housing a minimum of three jacks. The faceplate shall fit into a modular furniture raceway. Ultilize flat faceplates unless workspace requires an angled faceplate. An additional label will be required containing contact information. This additional label shall be permanently affixed to the faceplate.
  5. 106-Type Faceplate. Provide duplex mounting strips to house four work area jacks in a standard NEMA duplex electrical mounting fitted in a raceway, poke-through unit or flush floorbox, and all animal holding area rooms.
  6. Waterproof Faceplate. Provide Hubbell (5205WO) aluminum cast faceplate suitable for waterproof applications. The faceplate shall be installed horizontally at all outdoor, animal holding, cage wash areas and other moisture exposed areas.
  7. Stainless Steel Faceplate. Provide decorative stainless steel faceplate covers for locations where stainless steel wall outlets are required.
  8. Floorbox Faceplate. Provide an internal blank bracket to house combinations of work area jacks and optional LC connectors in a flush-mounted floorbox. The bracket shall be provided by the manufacturer of the flush floorbox and shall be designed to fit in the floorbox installed as a part of this project. Provide cutsheets for the floor boxes to be utilized on the project so the correct faceplate insert can be sources to support Panduit Mini-Com jacks. A solution that does not utilize Panduit Mini-Com jacks will not be installed and will require a different floor mount box to be used.
  9. Wireless Networking. Faceplates and enclosures required for supporting wireless networking will be specified on a case by case basis by Caltech. Location of faceplates for wireless need to be as close as practical to locations specified on the drawings. Locations which deviate in excess of 1 meters (3 feet) from the specified location need to be approved by Caltech.
  10. Single Communications Outlet (Wall Phone) - 6 conductor.
    1. Unless otherwise specified, each outlet will be configured with (1) RJ11 telephone connector terminated with the USOC wiring standard. This outlet shall be capable of supporting a wall-mounted phone.
    2. Provide (1) Category 6 distribution cable running from each outlet back to the patch panel in the Communications Rooms using cable tray and conduit infrastructure. Leave 12 inches of slack cable in wall behind wall mounted outlet to allow for retermination to support Voice over IP and other network services.
    3. At the closet end, terminate the first three pairs of each distribution cable on a RJ48 jack using the TIA-568B wiring scheme.
    4. At the termination frame end, terminate all four pairs of the cable onto the patch panel using the TIA-568B wiring scheme.
  11. Single Communications Outlet (Wall Phone) - 8 conductor (VoIP)
    1. Provide Keystone Phone plate with module to support mounting of wall phone while conforming with Panduit TX6 cabling requirements.
    2. Use Panduit TX6 Keystone Jack Module for termination instead of Mini-Comm jack due to faceplate design.
    3. Provide (1) Category 6 distribution cable running from each outlet back to the patch panel in the Communications Rooms using cable tray and conduit infrastructure.
    4. Installation to be certified consistent to Panduit TX6 extended warranty requirements.
  12. TV Outlet
    1. Unless otherwise specified, each duplex outlet will be configured with (1) F-Type coupler.
    2. Provide (1) RG-6 distribution cable running from each outlet back to the RJ45 patch panel in the CATV Closet using cable tray and conduit infrastructure.
    3. Terminate each RG-6 distribution cable on an F-Type jack.
    4. Provide (1) coaxial cable running from each outlet back to the CATV Closet using cable tray and conduit infrastructure.
    5. Terminate each coaxial distribution cable on an F-Type Connector at each end. Mount F-type connectors to blank 1U jack panel in television cable wiring closet which is a location separate from the MDF and IDFs located in the facility. CATV coaxial cable plant is not to be terminated in MDF or IDFs, only in CATV closet. CATV coaxial cable plant is not to transit the Voice and Data networking conduits, they must run through their own conduits and duct bank.
    6. Power meter and frequency sweep installed cable to certify 5MHz to 3GHz usability.
    7. Provide test results in electronic form.
  13. Quad Communications Outlet
    1. Unless otherwise specified, each quad outlet will be configured with (3) RJ45 connectors. Positions upper left and upper right are reserved for network, lower right corner is reserved for CATV.
    2. Provide (3) Category 6 distribution cables running from each outlet back to the RJ45 patch panel in the Communications Room (Distribution Frame) using the cable tray and conduit infrastructure.
    3. Terminate each Category 6 (Cat-6) distribution cable at each end on a RJ45 jack using the 568B wiring scheme.
  14. Sextuple Communications Outlet
    1. Unless otherwise specified, each sextuple outlet will be configured with (4) RJ45 connectors. Positions upper left, upper middle and upper right are reserved for network, lower right corner is reserved for telephone and lower right is reserved for CATV.
    2. Provide (4) Category 6 distribution cables running from each outlet back to the RJ45 patch panel in the Communications Room (Distribution Frame) using the cable tray and conduit infrastructure.
    3. Terminate each Category 6 (Cat-6) distribution cable at each end on a RJ45 jack using the 568B wiring scheme.
  15. Furniture Mounted Outlets
    1. Each desk will have (1) four-port faceplate. Provide (3) Category 6 distribution cables running from the faceplate back to the RJ45 patch panel in the Communications Room (Distribution Frame) using cable tray and conduit infrastructure.
    2. Terminate the Category 6 (Cat-6) distribution cables at each end on a RJ45 jack using the 568B wiring scheme.
  16. Raceway Outlets
    1. Each raceway data activation will have (1) four-port outlet mounting strap (106 frame). Provide (3) Category 6 distribution cables running from each mounting strap back to the RJ-45 patch panel in the Comminations Room using cable tray and conduit infrastructure.
    2. Terminate each Category 6 (Cat-6) distribution cable at each end on a RJ45 jack using the 568B wiring scheme.
  17. Floorbox Outlets
    1. Each floorbox will have (1) four-port 106 frame. The frame will support data and voice services. Provide (3) Category 6 distribution cables running from the modules back to the RJ-45 patch panel in the Communications Room using cable tray and conduit infrastructure.
    2. Terminate the Category 6 (Cat-6) distribution cables at each end on a RJ-45 jack using the 568B wiring scheme.
  18. Work Area Faceplates and Blanking Plates
    1. Carry out a visual inspection of the faceplates and blanking plates. Replace all damaged components.
    2. Ensure that all faceplate labels are installed correctly.

3.2 Horizontal Distribution Cable Installation

  1. Cable shall be installed in accordance with manufacturer’s recommendations and best industry practices.
  2. A pull cord (nylon; 1/8" minimum) shall be co-installed with all cable installed in any conduit.
  3. Cable raceways shall not be filled greater than the TIA/EIA-569-C maximum fill for the particular raceway type or 40%.
  4. Cables shall be installed in continuous lengths from origin to destination (no splices) except for transition points, or consolidation points.
  5. Where transition points, or consolidation points are allowed, they shall be located in accessible locations and housed in an enclosure intended and suitable for the purpose.
  6. The cable’s minimum bend radius and maximum pulling tension shall not be exceeded.
  7. If a J-hook or trapeze system is used to support cable bundles all horizontal cables shall be supported at a maximum of 48 to 60 inch (1.2 to 1.5 meter) intervals. At no point shall cable(s) rest on acoustic ceiling grids or panels.
  8. Horizontal distribution cables shall be bundled in groups of no more than 50 cables. Cable bundle quantities in excess of 50 cables may cause deformation of the bottom cables within the bundle and degrade cable performance.
  9. Cable shall be installed above fire-sprinkler systems and shall not be attached to the system or any ancillary equipment or hardware. The cable system and support hardware shall be installed so that it does not obscure any valves, fire alarm conduit, boxes, or other control devices.
  10. Cables shall not be attached to ceiling grid or lighting fixture wires. Where support for horizontal cable is required, the contractor shall install appropriate carriers to support the cabling.
  11. Any cable damaged or exceeding recommended installation parameters during installation shall be replaced by the contractor prior to final acceptance at no cost to the Owner.
  12. Cables shall be identified by a self-adhesive label in accordance with the System Documentation Section of this specification and ANSI/TIA/EIA-606. The cable label shall be applied to the cable behind the faceplate on a section of cable that can be accessed by removing the cover plate.
  13. Unshielded twisted pair cable shall be installed so that there are no bends smaller than four times the cable outside diameter at any point in the run and at the termination field.
  14. Pulling tension on 4-pair UTP cables shall not exceed 25-lbf for a four-pair UTP cable.

3.3 Horizontal Cross Connect Installation

  1. Cables shall be dressed and terminated in accordance with the recommendations made in the ANSI/TIA/EIA-568-C.0, ANSI/TIA/EIA-568-C.1 & ANSI/TIA/EIA-568-C2 standards, manufacturer's recommendations and best industry practices.
  2. Pair untwist at the termination shall not exceed 3.18 mm (0.125 inch).
  3. Bend radius of the cable in the termination area shall not exceed 4 times the outside diameter of the cable.
  4. Cables shall be neatly bundled and dressed to their respective panels or blocks. Each panel or block shall be fed by an individual bundle separated and dressed back to the point of cable entrance into the rack or frame.
  5. The cable jacket shall be maintained as close as possible to the termination point.
  6. Each cable shall be clearly labeled on the cable jacket behind the patch panel at a location that can be viewed without removing the bundle support ties. Cables labeled within the bundle, where the label is obscured from view shall not be acceptable.

3.4 Optical Fiber Termination Hardware

  1. Fiber slack shall be neatly coiled within the fiber splice tray or enclosure. No slack loops shall be allowed external to the fiber panel.
  2. Fiber optic service loop of no less than 10 meters is to be properly dressed and secured above the rack(s) for fiber optic interconnects (not applicable to fiber to the desktop installations).
  3. Each cable shall be individually attached to the respective fiber enclosure by mechanical means. The cables strength member shall be securely attached the cable strain relief bracket in the enclosure.
  4. Each fiber bundle shall be stripped upon entering the splice tray and the individual fibers routed in the splice tray.
  5. Each cable shall be clearly labeled at the entrance to the splice enclosure. Cables labeled within the bundle shall not be acceptable.
  6. A maximum of 24 strands of fiber shall be spliced in each tray.
  7. If spare strands are pulled, all spare strands shall be installed into spare splice trays. Note: All pulled fiber is to be terminated and tested.

3.5 Copper Termination Hardware

  1. Cables shall be dressed and terminated in accordance with the recommendations made in the ANSI/TIA/EIA-568-C.0 standard, manufacturer's recommendations and best industry practice.
  2. Pair untwist at the termination shall not exceed 3.18mm (0.125 inch).
  3. Bend radius of the cable in the termination area shall not exceed 4 times the outside diameter of the cable.
  4. Cables shall be neatly bundled and dressed to their respective panels or blocks. Each panel or block shall be fed by an individual bundle separated and dressed back to the point of cable entrance into the rack or frame.
  5. The cable jacket shall be maintained to within 25 mm (one inch) of the termination point.
  6. Each cable shall be clearly labeled on the cable jacket behind the patch panel at a location that can be viewed without removing the bundle support ties. Cables labeled within the bundle, where the label is obscured from view shall not be acceptable.

3.6 Labeling and Identification

  1. The contractor shall contact The Owner for the labelig scheme used on campus and submit for approval samples of the labeling system for the cable installation. The Owner will negotiate an appropriate labeling scheme with the successful contractor. At a minimum, the labeling system shall clearly identify all components of the system: racks, cables, panels and outlets. The labeling system shall designate the cables origin and destination and a unique identifier for the cable within the system. Racks and patch panels shall be labeled to identify the location within the cable system infrastructure. All labeling information shall be recorded on the as-built drawings and all test documents shall reflect the appropriate labeling scheme.
  2. All label printing will be machine generated by Panduit PanMark software and Panduit desktop and hand-held printers using indelible ink ribbons or cartridges. Self-laminating labels will be used on cable jackets, appropriately sized to the OD of the cable, and placed within view at the termination point on each end. Outlet, patch panel and wiring block labels shall be installed on, or in, the space provided on the device.Panduit heat shrik, machine printed labels are also acceptable.

3.7 Testing and Acceptance

  1. General
    1. All cables and termination hardware shall be 100% tested for defects in installation and to verify cabling system performance under installed conditions according to the requirements ofANSI/TIA/EIA-568-C.0 & ANSI/TIA/EIA-568-C2. All pairs of each installed cable shall be verified prior to system acceptance. Any defect in the cabling system installation including but not limited to cable, connectors, feed through couplers, patch panels, and connector blocks shall be repaired or replaced in order to ensure 100% usable conductors in all cables installed.
    2. All cables shall be tested in accordance with this document, the ANSI/TIA/EIA standards, the Panduit Certification Plus System Warranty guidelines and best industry practice. If any of these are in conflict, the Contractor shall bring any discrepancies to the attention of the project team for clarification and resolution.
  2. Copper Channel Testing:
    1. All twisted-pair copper cable links shall be tested for continuity, pair reversals, shorts, opens and performance as indicated below. Additional testing is required to verify Category performance. Horizontal cabling shall be tested using a level IIIe or level IV test unit for Category 6 performance compliance.
    2. Continuity - Each pair of each installed cable shall be tested using a test unit that shows opens, shorts, polarity and pair-reversals, crossed pairs and split pairs. Shielded/screened cables shall be tested with a device that verifies shield continuity in addition to the above stated tests. The test shall be recorded as pass/fail as indicated by the test unit in accordance with the manufacturers’ recommended procedures, and referenced to the appropriate cable identification number and circuit or pair number. Any faults in the wiring shall be corrected and the cable re-tested prior to final acceptance.
    3. Length - Each installed cable link shall be tested for installed length using a TDR type device. The cables shall be tested from patch panel to patch panel, block to block, patch panel to outlet or block to outlet as appropriate. The cable length shall not exceed 85 meters as specified in this document, superceding the maximum distances set forth in the ANSI/TIA/EIA-568-C.0 & ANSI/TIA/EIA-568-C2 Standards. Cable lengths shall be recorded, referencing the cable identification number and circuit or pair number. For multi-pair cables, the shortest pair length shall be recorded as the length for the cable.
    4. Category 6 Performance:
      1. Follow the Standards requirements established in ANSI/TIA/EIA-568-C.2
      2. A level III test unit is required to verify category 6 performances including:
        1. Wire map
        2. Resistance
        3. Characteristic impedance
        4. Length
        5. Propagation delay
        6. Delay skew
        7. Insertion loss (attenuation)
        8. NEXT (near-end crosstalk) and NEXT at the smart remote
        9. PSNEXT (Power sum near-end crosstalk loss)
        10. Return loss
        11. ACR-N (attenuation to crosstalk ratio at the near end) and ACR-N at the smart remote
        12. PS ACR-N (power-sum attenuation to crosstalk ratio) and PS ACR-N at the smart remote
        13. ACR-F (equal level far-end crosstalk)
        14. PS ACR-F (power-sum equal level far-end crosstalk)
  3. Fiber Testing
    1. Section 27 1323 and 27 1523 are the authoritative documents regarding Fiber Termination and Testing.
    2. All fiber testing shall be performed on all fibers in the completed end-to-end system. There shall be no splices unless clearly defined in an RFP. Testing shall consist of an end-to-end power meter test performed per TIA/EIA-526-14-B. The system loss measurements shall be provided at 850 and/or 1300 nanometers for multimode fibers and 1310 and/or 1550 nanometers for single mode fibers. These tests also include continuity checking of each fiber.
    3. For horizontal cabling system using multimode optical fiber, attenuation shall be measured in one direction at either 850 nanometer (nm) or 1300 nm using an LED light source and power meter.
    4. Backbone multimode fiber cabling shall be tested at both 850 nm and 1300 nm (or 1310 and 1550 nm for singlemode) in one direction.
    5. Test set-up and performance shall be conducted in accordance with ANSI/TIA/EIA-526-14-B, Method B.
    6. OTDR tests shall be performed for all fibers.
    7. Where links are combined to complete a circuit between devices, the Contractor shall test each link from end to end to ensure the performance of the system. ONLY BASIC LINK TEST IS REQUIRED. The contractor can optionally install patch cords to complete the circuit and then test the entire channel. The test method shall be the same used for the test described above. The values for calculating loss shall be those defined in the ANSI/TIA/EIA Standard.
    8. Attenuation testing shall be performed with a stable launch condition using two-meter jumpers to attach the test equipment to the cable plant. The light source shall be left in place after calibration and the power meter moved to the far end to take measurements.

3.8 System Documentation

  1. Upon completion of the installation, the telecommunications contractor shall provide three (3) full documentation sets to the Engineer for approval. Documentation shall include the items detailed in the sub-sections below.
  2. Documentation shall be submitted within ten (10) working days of the completion of each testing phase. This is inclusive of all test results and draft as-built drawings. Draft drawings may include annotations done by hand. Machine generated (final) copies of all drawings shall be submitted within 30 working days of the completion of each testing phase. At the request of the Engineer, the telecommunications contractor shall provide copies of the original test results.
  3. The Engineer may request that a 10% random field re-test be conducted on the cable system, at no additional cost, to verify documented findings. Tests shall be a repeat of those defined above. If findings contradict the documentation submitted by the telecommunications contractor, additional testing can be requested to the extent determined necessary by the Engineer, including a 100% re-test. This re-test shall be at no additional cost to the Owner.
  4. Test Results documentation shall be provided on disk/CD/digital format within three weeks after the completion of the project. The disk shall be clearly marked on the outside front cover with the words “Project Test Documentation”, the project name, and the date of completion (month and year). The results shall include a record of test frequencies, cable type, conductor pair and cable (or outlet) I.D., measurement direction, reference setup, and crew member name(s). The test equipment name, manufacturer, model number, serial number, software version and last calibration date will also be provided at the end of the document. Unless the manufacturer specifies a more frequent calibration cycle, an annual calibration cycle is anticipated on all test equipment used for this installation. The test document shall detail the test method used and the specific settings of the equipment during the test as well as the software version being used in the field test equipment.
  5. The field test equipment shall meet the requirements of ANSI/TIA/EIA-568-C.0, ANSI/TIA/EIA-568-C.1, ANSI/TIA/EIA-568-C.2 including applicable TSB’s and amendments. The appropriate level III tester shall be used to verify Category 6 cabling systems.
  6. Printouts generated for each cable by the wire (or fiber) test instrument shall be submitted as part of the documentation package. Alternately, the telecommunications contractor may furnish this information in electronic form (compact disc). These discs shall contain the electronic equivalent of the test results as defined by the bid specification and be of a format readable from Microsoft Word or Microsoft Excel. The reporting of results in this format is not a substitute for native formatted test results.
  7. When repairs and re-tests are performed, the problem found and corrective action taken shall be noted, and both the failed and passed test data shall be documented.
  8. The As-Built drawings are to include cable routes and outlet locations. Their sequential number as defined elsewhere in this document shall identify outlet locations. Numbering, icons, and drawing conventions used shall be consistent throughout all documentation provided. The Owner will provide floor plans in paper and electronic (DWG, AutoCAD rel. 2004) formats on which as-built construction information can be added. These documents will be modified accordingly by the telecommunications contractor to denote as-built information as defined above and returned to the Owner. Numbering, icons, pathways and other drawing conventions are to be assigned their own individual AutoCAD layer.
  9. The Contractors shall annotate the base drawings and return a hard copy (same plot size as originals) and electronic (AutoCAD rel. 2004 or as agreed to by Caltech).

End Section